Customization: | Available |
---|---|
Electricity Type: | AC |
Phase: | 3 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
LC2K and LP2K Reversing contactors for motor control
6A to 16A in utilisation category AC-3 and 20A in utilisation category AC-1
Control circuit: a.c. and d.c.
Model Number |
Number of poles |
Auxiliary contacts |
Rated current | Standard power ratings of 3-phase motors |
Control Circuit Voltage |
Mounting type |
|||||
in category AC-3 | in category AC-3 | ||||||||||
NO | NC | up to 400V |
660V | 220V 240V |
380V 415V |
440V 500V |
660V 690V |
||||
LC2-K0610 | 3 pole | 1 | - | 6A | 5A | 1.5kW | 2.2kW | 3kW | 3kW | AC (as per below table) |
Din rail or screw fixing |
LC2-K0601 | - | 1 | |||||||||
LC2-K0910 | 1 | - | 9A | 7.5A | 2.2kW | 4kW | 4kW | 4kW | |||
LC2-K0901 | - | 1 | |||||||||
LC2-K1210 | 1 | - | 12A | 10A | 3kW | 5.5kW | 5.5kW | 4kW | |||
LC2-K1201 | - | 1 | |||||||||
LC2-K1610 | 1 | - | 16A | 12A | 3kW | 7.5kW | 7.5kW | 4kW | |||
LC2-K1601 | - | 1 | |||||||||
LC2-K06105 | 3 pole | 1 | - | 6A | 5A | 1.5kW | 2.2kW | 3kW | 3kW | Solder pins for PCB (printed circuit board) |
|
LC2-K06015 | - | 1 | |||||||||
LC2-K09105 | 1 | - | 9A | 7.5A | 2.2kW | 4kW | 4kW | 4kW | |||
LC2-K09015 | - | 1 | |||||||||
LC2-K12105 | 1 | - | 12A | 10A | 3kW | 5.5kW | 5.5kW | 4kW | |||
LC2-K12015 | - | 1 | |||||||||
LC2-K16105 | 1 | - | 16A | 12A | 3kW | 7.5kW | 7.5kW | 4kW | |||
LC2-K16015 | - | 1 | |||||||||
LP2-K0610 | 3 pole | 1 | - | 6A | 5A | 1.5kW | 2.2kW | 3kW | 3kW | DC (as per below table) |
Din rail or screw fixing |
LP2-K0601 | - | 1 | |||||||||
LP2-K0910 | 1 | - | 9A | 7.5A | 2.2kW | 4kW | 4kW | 4kW | |||
LP2-K0901 | - | 1 | |||||||||
LP2-K1210 | 1 | - | 12A | 10A | 3kW | 5.5kW | 5.5kW | 4kW | |||
LP2-K1201 | - | 1 | |||||||||
LP2-K1610 | 1 | - | 16A | 12A | 3kW | 7.5kW | 7.5kW | 4kW | |||
LP2-K1601 | - | 1 | |||||||||
LP2-K06105 | 3 pole | 1 | - | 6A | 5A | 1.5kW | 2.2kW | 3kW | 3kW | Solder pins for PCB (printed circuit board) |
|
LP2-K06015 | - | 1 | |||||||||
LP2-K09105 | 1 | - | 9A | 7.5A | 2.2kW | 4kW | 4kW | 4kW | |||
LP2-K09015 | - | 1 | |||||||||
LP2-K12105 | 1 | - | 12A | 10A | 3kW | 5.5kW | 5.5kW | 4kW | |||
LP2-K12015 | - | 1 | |||||||||
LP2-K16105 | 1 | - | 16A | 12A | 3kW | 7.5kW | 7.5kW | 4kW | |||
LP2-K16015 | - | 1 | |||||||||
Dimension, mounting:
Schemes: