Customization: | Available |
---|---|
Electricity Type: | AC |
Phase: | 3 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
LC2-D LC2-F Reversing Contactor Equivalent to Chint NC1-N NC1-2 AC Contactor
Application
LC2-D LC2-F mechanical interlocking contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz, current 620A, for convertible controlling the motor. This mechanical interlocking device ensures contact changeover of the two convertible contactors. It conforms to IEC60947-4-1.
Specification
Type | Rated current AC-3(A) |
Controlled power (KW) | ||||
220V | 380V | 415V | 440V | 660V | ||
LC2-D09 | 9 | 2.2 | 4 | 4 | 4 | 5.5 |
LC2-D12 | 12 | 5.5 | 5.5 | 5.5 | 5.5 | 7.5 |
LC2-D18 | 18 | 7.5 | 7.5 | 9 | 9 | 10 |
LC2-D25 | 25 | 5.5 | 11 | 11 | 11 | 15 |
LC2-D32 | 32 | 7.5 | 15 | 15 | 15 | 18.5 |
LC2-D40 | 40 | 18.5 | 18.5 | 22 | 22 | 30 |
LC2-D50 | 50 | 15 | 22 | 25 | 30 | 33 |
LC2-D65 | 63 | 18.5 | 30 | 37 | 37 | 37 |
LC2-D80 | 80 | 22 | 37 | 45 | 45 | 45 |
LC2-D95 | 95 | 22 | 45 | 45 | 45 | 41 |
LC2-D115 | 115 | 30 | 55 | 59 | 59 | 80 |
LC2-D150 | 150 | 40 | 75 | 80 | 80 | 100 |
LC2-D170 | 170 | 55 | 90 | 100 | 100 | 110 |
LC2-D205 | 205 | 63 | 110 | 110 | 110 | 129 |
LC2-D245 | 245 | 75 | 132 | 132 | 132 | 160 |
LC2-D300 | 300 | 100 | 160 | 200 | 200 | 220 |
LC2-D410 | 410 | 110 | 220 | 250 | 250 | 280 |
LC2-D475 | 475 | 147 | 265 | 280 | 280 | 355 |
LC2-D620 | 620 | 200 | 335 | 400 | 400 | 450 |
Type | Number of Poles | Rated Current AC-3(A) |
Rated Current In/A |
Controlled power(KW) | |
220V | 380V | ||||
LC2-F115 | 3P | 115 | 250 | 200 | 55 |
LC2-F1154 | 4P | 115 | 250 | 200 | 55 |
LC2-F150 | 3P | 150 | 355 | 250 | 75 |
LC2-F1504 | 4P | 150 | 355 | 250 | 75 |
LC2-F185 | 3P | 185 | 425 | 275 | 90 |
LC2-F1854 | 4P | 185 | 425 | 275 | 90 |
LC2-F225 | 3P | 225 | 500 | 315 | 110 |
LC2-F2254 | 4P | 225 | 500 | 315 | 110 |
LC2-F265 | 3P | 265 | 630 | 350 | 132 |
LC2-F2654 | 4P | 265 | 630 | 350 | 132 |
LC2-F330 | 3P | 330 | 800 | 400 | 160 |
LC2-F3304 | 4P | 330 | 800 | 400 | 160 |
LC2-F400 | 3P | 400 | 800 | 500 | 200 |
LC2-F4004 | 4P | 400 | 800 | 500 | 200 |
LC2-F500 | 3P | 500 | 1000 | 700 | 250 |
LC2-F5004 | 4P | 500 | 1000 | 700 | 250 |
LC2-F630 | 3P | 630 | 1250 | 1000 | 335 |
LC2-F6304 | 4P | 630 | 1250 | 1000 | 335 |
LC2-F800 | 3P | 800 | 1250 | 1000 | 400 |
LC2-D LC2-F mechanical interlocking contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz, current 620A, for convertible controlling the motor. This mechanical interlocking device ensures contact changeover of the two convertible contactors. It conforms to IEC60947-4-1.
LC2-D LC2-F mechanical interlocking contactor is suitable for using in the circuits up to the rated voltage 660V AC 50Hz, current 620A, for convertible controlling the motor. This mechanical interlocking device ensures contact changeover of the two convertible contactors. It conforms to IEC60947-4-1.